|
INPUT REQUIREMENTS
- 100 VAC-240VAC ± 10% /47Hz to 63 Hz
input
- (a) 30A max. @ 115VAC under the
worst case load and cold start
- (b) 60A max. @ 230VAC under the
worst case load and cold start
- 0.5 RMS Max. at full load and 115
VAC input
- 0.25 RMS Max. at full load and 230
VAC input
- 0.5 min. at full load and 115 VAC
input
- 70% min. at specified line voltages,
outputs at full load
The output shall be isolated from the
input and the supply shall be able to withstand without
permanent damage.Power line transients as defined in IEC
801-4 or IEC 801-5, line to neutral 1 kV line to neutral
with floating ground, 2kV.
OUTPUT REQUIREMENTS
- 1% measure at 115VAC or 230VAC±15%
- ±5% measure at all output from min.
load to max. load
at 115VAC ,60Hz.
- ±5% max. at power turn on and turn
off measured at
115 VAC or 230 VAC at full load.
- 200 ms max at Vin = 115 VAC and full
load.
M.T.B.F.
M.T.B.F. shall be a min. of 100,000 hours
when operated at
25 °C ambient, running at 100% duty cycle with the following
line and load conditions:
Outputs loaded at 80% of maximum load as
defined in the specifications above.
The input line Voltage will be set at any
level specified in the input Voltage range.
Test verification will be confirmed using
either a one-sided (zero failure) 90% confidence level test,
or by observed test results as defined below.
Unit failure shall be defined as any unit
failing to provide output Voltage or short circuit
protection, or exceeding the ripple specification limits
during the test.
The test environment shall be 30 ± 2° C
with input line Voltage at 230VAC. The output loads will be
set at 80% of max. load levels defined in the
specifications.
The test sample shall consist of
200 units for the initial test cycle. Units will be test
verified daily, and any failure during the test will be
replaced with a new sample unit. The M.T.B.F. for the
observed test results is defined by equation(1):
(1) Observed M.T.B.F. = (nt)/#Failure
When no failures occur in a test, the 90%
confidence M.T.B.F. is defined by equation (2):
(2) M.T.B.F.>
nt/In a
t= time in test
n= sample size
Confidence Level=1-a
|
PROTECTION
- 110-160% of rated power. Auto
recovery.
- For any output shorted to ground,
grounded output will not damage this power supply. A
short to the ground will be defined as a maximum of 0.1
OHM as seen by the output connection of the power
supply.
ELECTROMAGNETIC REQUIREMENTS
The radiated and conducted emissions of
this adapter comply with the requirements of United States
Federeal Communication Commission (FCC) part 15, class B and
with CISPR 22.and CISPR 22.
SAFETY REQUIREMENTS
- The power supply is approved
for the following:
- HI POT A: Primary - Secondary (FG) -
1500VAC for 60 seconds or DC equivalent 2121VDC for 60
seconds. If DC voltage used for test, the voltage should
ramp up and down with 1 sec. rise time.
- HI POT B: Transformer Primary -
Secondary - 3750VAC for 1 minute (component level).
ENVIRONMENT
- (1) Operating temp. is 0 °C to 40°C.
- (2) Storage temp. is -20°C to 85° C.
- (3) Operating humidity is 15% to 85%
RH
- (4) Storage humidity is 5% to 90% RH
Operating: 10G, 11 ms, half sine, one
shock input in each of three mutually perpendicular axis,
for a total of six shock inputs.
Storage: 100G, trapezoid,180 IN/S
velocity change one shock imput per direction in each of
three mutually perpendicular axis, for a total of six shock
inputs.
Operating: 0.75G
zero to peak, 5 to 500Hz, 0.5 octaves/minute, one cycle, 5
to 500 to 5 Hz per axis in each of three mutually
perpendicular axis.
Storage: 1.5G zero to peak,5 to
500Hz, 0.5 octaves/minute, one cycle,5 to 500 to 5 Hz per
axis in each of three mutually perpendicular axis for a
total duration of three hours.
DIMENSIONS & WEIGHT
- LxWxH: 114mm x 68mm x 40mm
- Weight: 560 g Typical
|